ULTIMA MOS 5 HART
7
Code Class Description
5 Error Too Few Data Bytes Received
6 – 15 N/A Undefined
16 Error Access Restricted
17 – 127 N/A Undefined
10.3 Command #137: Set Warn Level
This command sets the Warn level.
Request Data Bytes
Byte Format Description
0 Unsigned-8 Alarm Warn level, % of FS
Response Data Bytes
Byte Format Description
0 Unsigned-8 Alarm Warn level, % of FS
Command-Specific Response Codes
Code Class Description
0 Success No Command-Specific Errors
1 – 2 N/A Undefined
3 Error Passed Parameter Too Large
4 N/A Undefined
5 Error Too Few Data Bytes Received
6 – 15 N/A Undefined
16 Error Access Restricted
17 – 127 N/A Undefined
10.4 Command #139: Reset Alarm
This command resets the latching Warn and Alarm relay.
Request Data Bytes
Byte Format Description
None N/A N/A
Response Data Bytes
Byte Format Description
None N/A N/A
Command-Specific Response Codes